Store the battery in a dry place.
Recycle exhausted batteries meeting the environmental standards.
Transport of lithium batteries or equipment with installed lithium batteries:
The transport and handling instructions of the battery producer must be observed.
The transport regulations for transport of lithium batteries must be observed e.g. for trans-
port by road or air.
The forwarder must be informed if batteries are contained in the shipment.
Assembling and electrical connection of the battery is described in chapters TA561-RTC real-
time clock adaptor
Ä
Chapter 2.5.5.3 “TA561-RTC - Real-time Clock Adaptor ” on page 1225
and TA562-RS-RTC serial RS-485 and real-time clock adaptor
Ä
Chapter 2.5.5.6 “TA562-RS-
RTC - Adaptor with Serial RS-485 (COM2) and Real-time Clock ” on page 1233.
The battery lifetime is the time the battery can operate the RTC while the CPU is not powered.
The typical lifetime is 300 days (at 25 °C).
As long as the CPU is powered, the battery will only be discharged by its own leakage current.
The battery must meet die following technical data:
Parameter Value
Battery designation CR2032
Description Manganese dioxide button cell, primary cell,
not rechargeable
Nominal voltage 3 VDC
Capacity 230 mAh (measured with 5.6 kW load at
20 °C, discharging down to 2.0 V)
Typical lifetime (at 25 °C, CPU not powered) 300 days
Temperature range ³ 0 °C ...+70 °C
Diameter 20 mm
Height 3.2 mm
2.5.5.8 TA563-TA565 - Terminal Blocks
These terminal blocks must only be used with AC500-eCo I/O Modules and
AC500-eCo processor modules.
Transport
Electrical Con-
nection
Battery Lifetime
Technical Data
System Assembly, Construction and Connection
AC500-eCo > Handling of Accessories
2019/04/17 3ADR010121, 13, en_US 1241