Channel Parameters for the Analog Outputs (2x)
Name Value Internal value Internal value,
type
Default
Output 0,
Channel configu-
ration
see table
3
) see table
3
)
BYTE 0
Output 0, Check
channel
see table
4
) see table
4
)
BYTE 0
Output 0, Substi-
tute value
see table
5
) see table
5
)
WORD 0
Output 1,
Channel configu-
ration
see table
3
) see table
3
)
BYTE 0
Output 1, Check
channel
see table
4
) see table
4
)
BYTE 0
Output 1, Substi-
tute value
see table
5
) see table
5
)
WORD 0
Table 123: Channel Configuration
3
)
Internal value Operating modes of the analog outputs, individually configurable
0 (default) Not used
128 -10 V...+10 V
129 0...20 mA
130 4...20 mA
Table 124: Channel Monitoring
4
)
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Table 125: Substitute Value
5
)
Intended behaviour of
output channel when the
control system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn
off
Last value 5 sec 0
Last value for 10 s and then
turn off
Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s and
then turn off
Substitute value 5 sec Depending on configuration
Substitute value for 10 s and
then turn off
Substitute value 10 sec Depending on configuration
Device Specifications
Communication Interface Modules (S500) > CS31
2019/04/173ADR010121, 13, en_US798