LED Color OFF ON Flashing
S-ERR Red No error Internal error --
I/O-Bus Green No expansion
modules con-
nected or com-
munication error
Expansion mod-
ules connected
and operational
---
Table 164: States of the 29 Process LEDs:
LED Color OFF ON Flashing
DC0 to DC7 Yellow Input/Output is
OFF
Input/Output is
ON
--
DI8 to DI15 Yellow Input is OFF Input is ON (the
input voltage is
even displayed if
the supply
voltage is OFF)
--
DO8 to DO15 Yellow Output is OFF Output is ON --
UP Green Process supply
voltage missing
Process supply
voltage OK and
initialization fin-
ished
--
UP3 Green Process supply
voltage missing
Process supply
voltage OK
--
CH-ERR1 to CH-
ERR3
Red No error or
process supply
voltage missing
Internal error Error on one
channel of the
corresponding
group
1.7.5.2.10 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Technical Data of the Module
Parameter Value
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Electrical isolation PROFIBUS interface against the rest of the
module
Inrush current from UP (at power up) On request
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/173ADR010121, 13, en_US998