Output Ranges Voltage and Current
Range -10...+10 V 0...20 mA 4...20 mA Digital value
Decimal Hex.
Overflow 0 V 0 mA 0 mA > 32511 > 7EFF
Measured
value too high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
32511
:
27649
7EFF
:
6C01
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0,0007 mA
20.0000 mA
:
4.0006 mA
27648
:
1
6C00
:
0001
0.0000 V 0.0000 mA 4.0000 mA 0 0000
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
-1
-6912
-27648
FFFF
E500
9400
Measured
value too low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
-27649
:
-32512
93FF
:
8100
Underflow 0 V 0 mA 0 mA < -32512 < 8100
The represented resolution corresponds to 16 bits.
1.7.2.2.12 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical Data of the Module
Parameter Value
Process supply voltage UP:
Rated value 24 VDC
Protection against reverse voltage Yes
Rated protection fuse at UP 10 A fast
Current consumption
From UP 0.07 A + max. 0.5 A per output
Device Specifications