Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Galvanic isolation Yes, between the channels and the rest of the
module
Isolated groups 8 (1 channel per group)
Current consumption from 24 VDC power
supply at the L+/UP and M/ZP terminals of
the CPU/bus module
Ca. 10 mA
Max. power dissipation within the module On request
Weight Ca. 135 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switch-gear cabinet.
Technical Data of the Digital Inputs
Parameter Value
Number of channels per module 8 AC inputs (100-240 VAC)
Distribution of the channels into groups 8 (1 channel per group)
Input voltage range 0 VAC..264 VAC (47 Hz...63 Hz)
Input current per channel (typically at 25 °C) <5 mA (at 40 VAC)
>6 mA (at 159 VAC, 50 Hz)
>7 mA (at 159 VAC, 60 Hz)
Connections of the channels I0 to I7 Terminals 1, 3, 5, 7, 10, 12, 14, 16
Reference potential for the channels I0 to I7 Terminals 2, 4, 6, 8, 11, 13, 15, 17
Indication of the input signals 1 yellow LED per channel; the LED is ON
when the input signal is high (signal 1)
Input type according to EN 61131-2 Type 1
Input signal range
Signal 0 (max.) 20 VAC
Undefined signal 20 VAC < U < 79 VAC
Signal 1 (min.) 79 VAC
Input delay
Signal 0 -> 1 Typ. 15 ms
Signal 1 -> 0 Typ. 30 ms
Input data length 1 byte
Max. permissible leakage current (at 2-wire
proximity switches)
1 mA
Max. cable length
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US212