EasyManua.ls Logo

ABB AC500 PLC - 1.7.1.2.10 Measuring Ranges; Input Ranges Voltage, Current and Digital Input; Input Range Resistor

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.7.1.2.10 Measuring Ranges
Input Ranges Voltage, Current and Digital Input
Range 0...10 V -10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal Hex.
Overflow >11.7589 >11.7589 >23.5178 >22.8142 32767 7FFF
Measured
value too
high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
: 6C01
Normal
range
Normal
range or
measured
value too
low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
On 27648
:
1
6C00
:
0001
0.0000 0.0000 0 4 Off 0 0000
-0.0004
-1.7593
-0.0004
:
:
:
-10,0000
3.9994
:
0
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
: 8100
Underflow <0.0000 <-11.7589 <0.0000 <0.0000 -32768 8000
The represented resolution corresponds to 16 bits.
Input Range Resistor
Range Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Overflow > 450.0 °C > 160.0 °C 32767 7FFF
Measured value
too high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
800
:
701
0320
:
02BD
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17 3ADR010121, 13, en_US 731

Table of Contents

Related product manuals