Range -10...+10 V 0...20 mA 4...20 mA Digital value
Decimal Hex.
Measured
value too low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
-27649
:
-32512
93FF
:
8100
Underflow 0 V 0 mA 0 mA < -32512 < 8100
The represented resolution corresponds to 16 bits.
1.7.4.1.10 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Technical Data of the Module
Parameter Value
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Electrical isolation Ethernet interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Ethernet 10/100 base-TX, internal switch, 2 x RJ45
socket
Setting of the IP address With ABB IP config tool and 2 rotary switches at
the front side of the module
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/17 3ADR010121, 13, en_US 911