Range -2.5 ...
+2.5 V
-5 ... +5
V
0 ... 5 V 0 ... 10 V 0 ... 20
mA
4 ... 20
mA
Digital value
Decimal Hex.
Normal
range or
meas-
ured
value too
low
0.0000 0.0000 0.0000 0.0000 0 4 0 0000
:
-0.0014
:
:
:
-2.5000
:
-0.0029
:
:
:
-5.0000
3.9942
:
:
0
-10
-16
-4864
-6912
:
-27648
FFF6
FFF0
ED00
E500
:
9400
Meas-
ured
value too
low
-2.5014
:
-2.9398
-5.0029
:
-5.8795
-27664
:
-32512
93F0
:
8100
Under-
flow
<-2.9398 <-5.8795 <-0.0300 <-0.0600 <-0.1200 <-0.1200 -32768 8000
The represented resolution corresponds to 12 bits respectively 11 bits plus sign.
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 19 for L+ (+24 VDC) and terminal 20
for M (0 V)
Rated value 24 VDC
Current consumption via L+ terminal 0.1 A
Inrush current (at power up)
0.05 A
2
s
Max. ripple 5 %
Protection against reversed voltage Yes
Protection fuse for L+ Recommended
Current consumption from 24 VDC power
supply at the terminals UP/L+ and ZP/M of the
CPU/bus module
Ca. 10 mA
Galvanic isolation No
Surge-voltage (max.) 35 VDC for 0.5 s
Max. power dissipation within the module 2.7 W
Weight Ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switch-gear cabinet.
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 403