EasyManua.ls Logo

ABB AC500 PLC - Ordering Data; 1.5.1.1.2 DC562 - Digital Input;Output Module

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Rated current (all channels together,
max.)
1.6 A
Lamp load (max.) Not applicable
Max. leakage current with signal 0 < 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 1 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to
load specification
Switching frequency
With inductive loads Max. 0.5 Hz
Short-circuit-proof / overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 VDC
signals
Yes
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering Data
Part No. Description Product Life Cycle Phase *)
1TNE 968 902 R2001 DC561, digital input/output module,
16 configurable inputs/outputs,
transistor output, interfast connector
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.5.1.1.2 DC562 - Digital Input/Output Module
16 configurable digital inputs/outputs in 1 group, 24 VDC
Module-wise electrically isolated
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 179

Table of Contents

Related product manuals