Parameter Value
Rated current (all channels together,
max.)
1.6 A
Lamp load (max.) Not applicable
Max. leakage current with signal 0 < 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 1 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to
load specification
Switching frequency
With inductive loads Max. 0.5 Hz
Short-circuit-proof / overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 VDC
signals
Yes
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering Data
Part No. Description Product Life Cycle Phase *)
1TNE 968 902 R2001 DC561, digital input/output module,
16 configurable inputs/outputs,
transistor output, interfast connector
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.5.1.1.2 DC562 - Digital Input/Output Module
● 16 configurable digital inputs/outputs in 1 group, 24 VDC
● Module-wise electrically isolated
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 179