3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 = expansion
1...10
Channel error: I/O bus or FBP = module type (2 = DO); COM1/COM2: 1...10 =
expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
1.6.2.1.8 State LEDs
During the power-on procedure, the module initializes automatically. All LEDs (except the LEDs
for the signal states) are on during the initialization.
LED State Color LED = OFF LED = ON LED flashes
A0, B0, Z0 Encoder 0
inputs
Yellow Input ON Input OFF LED follows
the state of the
inputs,
depending on
frequency
A1, B1, Z1 Encoder 1
inputs
Yellow Input ON Input OFF LED follows
the state of the
inputs,
depending on
frequency
I3 and I11 Digital inputs Yellow Input = ON
(the input
voltage is
even dis-
played if the
supply
voltage is
OFF).
Input = OFF ---
C4 to C7
and
C12 to C15
Configurable
digital inputs/
outputs
Yellow Input/output
= ON (the
input voltage
is even dis-
played if the
supply
voltage is
OFF).
Input/output =
OFF
---
O0 and O1 Digital PWM
outputs
Yellow Output = ON Output = OFF LED follows
the state of the
outputs,
depending on
frequency and
operation
mode
5V0 and
5V1
Power supply
for encoders
Green Configura-
tion ON and
power 5-V-
power ready
Configuration
OFF or power
failure
Power supply
outputs are
short-circuited
UP Process
supply
voltage
Green Process
voltage OK
Process
voltage is
missing
---
Device Specifications