ABB AC500 PLC - Connection of Passive-type Analog Sensors (Current) to the Analog Inputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 180: Connection of active-type sensors (voltage) with no electrically isolated power supply
to the analog inputs
CAUTION!
Risk of faulty measurements!
The minus pole at the sensors must not have a too big potential difference with
respect to ZP (max. ± 1 V).
Make sure that the potential difference never exceeds ± 1 V (also not with long
cable lengths).
The following measuring ranges can be configured
Ä
Chapter 1.7.4.1.7 “Parameterization”
on page 897 and
Ä
Chapter 1.7.4.1.9 “Measuring Ranges” on page 909.
Voltage 0...10 V 1 channel used
Voltage -10 V...+10 V 1 channel used
The function of the LEDs is described under Diagnosis and displays / Displays
Ä
Chapter
1.7.4.1.8 “Diagnosis and State LEDs” on page 903.
To avoid error messages from unused analog input channels, configure them as "unused".
Connection of Passive-type Analog Sensors (Current) to the Analog Inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/173ADR010121, 13, en_US890