Technical Data of the Fast Counter
Parameter Value
Used inputs Terminal 2.0 (DI0), 2.1 (DI1)
Used outputs Terminal 3.0 (DO0)
Counting frequency Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Detailed description See Fast Counter
Operating modes See Operating Modes
1.7.6.2.11 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 220 600 R0001 CI501-PNIO (V3), PROFINET bus
module, 8 DI, 8 DO, 4 AI and 2 AO
Active
1SAP 420 600 R0001 CI501-PNIO-XC (V3), PROFINET bus
module, 8 DI, 8 DO, 4 AI and 2 AO,
XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.7.6.3 CI502-PNIO (-XC)
8 digital inputs 24 VDC
8 digital outputs 24 VDC, 0.5 A max.
8 configurable digital inputs/outputs 24 VDC, 0.5 A max.
Module-wise electrically isolated
Fast counter
XC version for usage in extreme ambient conditions available