1
)
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The FBP diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1...10 = decentralized communication interface module
1...10, ADR = Hardware address (e.g. of the DC551)
3
)
With "Module" the following allocation applies dependent of the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or FBP = module type (4 = DC); COM1/COM2:
1...10 = expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED State Color LED = OFF LED = ON LED flashes
Outputs
O0...O31
Digital output Yellow Output =
OFF
Output = ON --
UP Process
supply
voltage
24 VDC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
CH-ERR1 Channel
error, error
messages in
groups (dig-
ital outputs
combined
into the
groups 1, 2,
3, 4)
Red No error or
process
supply
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
corresponding
group (e.g.
short circuit at
an output)
CH-ERR2 Red
CH-ERR3 Red
CH-ERR4 Red
CH-ERR *) Module error Red -- Internal error --
*) All of the LEDs CH-ERR1 to CH-ERR4 light up together
Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US358