NOTICE!
Risk of damaging the PLC modules!
The PLC modules must not be removed while the plant is connected to a power
supply.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove or replace a module.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply and process voltage) are
switched off before you begin with operations at the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
The module provides several diagnosis functions
Ä
Chapter 1.5.2.1.2.6 “Diagnosis”
on page 411.
The following figures show the electrical connection of RTDs to the inputs of the analog input
module AI562.
24 VDC
+
10
11
O0+
I0+
13
O1+
12
I0
14
I1+
15
I1
16
FE
17
FE
18
FE
19
UP
20
ZP
24 VDC
+
10
11
O0+
I0+
13
O1+
12
I0
14
I1+
15
I1
16
FE
17
FE
18
FE
19
UP
20
ZP
2-wires input 3-wires input
With 2-wires connection, the resistance of the connection wires influences the
accuracy of the measured value. Use 3-wires connection to achieve the guaran-
teed measuring accuracy.
The meaning of the LEDs is described in the Displays section
Ä
Chapter 1.5.2.1.2.7 “State
LEDs” on page 412.
I/O Configuration
The analog input module AI562 does not store configuration data itself.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 409