1.7.6.5.4 Assignment of the Ethernet Ports
The terminal unit for the communication interface module provides two Ethernet interfaces with
the following pin assignment:
Table 189: Pin assignment RJ45 jack:
Interface Pin Signal Description
1 TxD+ Transmit data +
2 TxD- Transmit data -
3 RxD+ Receive data +
4 NC not used
5 NC not used
6 RxD- Receive data -
7 NC not used
8 NC not used
Shield Cable shield Functional earth
For further information regarding wiring and cable types see chapter Ethernet
Ä
Chapter 2.6.4.10 “Ethernet Connection Details” on page 1288.
1.7.6.5.5 Addressing
The module reads the position of the rotary switches only during power-up, i. e.
changes of the switch position during operation will have no effect until the next
module initialization.
1.7.6.5.6 I/O Configuration
The CI506-PNIO stores some PROFINET configuration parameters:
Slave station name
Slave station type
IP address configuration
MAC address
Production data
No more configuration data is stored. The serial interfaces and the CANopen interface is config-
ured via software. For details, refer to Parameterization
Ä
Chapter 1.7.6.5.7 “Parameterization”
on page 1090.