Group Parameters for the Analog Part
Name Value Internal value Internal value,
type
Default
Analog data
format
Standard 0 BYTE 0
Behaviour AO at
comm. error *)
Off
Last value
Last value 5 s
Last value 10 s
Substitute value
Substitute value
5 s
Substitute value
10 s
0
1
6
11
2
7
12
BYTE 0
*) The parameter Behaviour AO at comm. error is only analyzed if the Failsafe-mode is ON.
Channel Parameters for the Analog Inputs (4x)
Name Value Internal value Internal value,
type
Default
Input 0, channel
configuration
see
1
) see
1
)
BYTE 0
Input 0, check
channel
see
2
) see
2
)
BYTE 0
: : : : :
: : : : :
Input 3, channel
configuration
see
1
) see
1
)
BYTE 0
Input 3, channel
configuration
see
2
) see
2
)
BYTE 0
Internal value Operating modes of the analog inputs, individually configurable
0 (default) Not used
1 0...10 V
2 Digital input
3 0...20 mA
4 4...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50...+400 °C
9 3-wire Pt100 -50...+400 °C *)
10 0 V...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50...+70 °C
15 3-wire Pt100 -50...+70 °C *)
Channel Config-
uration
1
)
Communication Interface Modules (S500) > EtherCAT
2019/04/17 3ADR010121, 13, en_US 845