EasyManua.ls Logo

ABB AC500 PLC - 2.6.4.7 Serial Interface COM2 of the Terminal Bases

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Slave at the bus line end, bus termination with 120 Ω resistors
2 Master within the bus line, pull-up and pull-down activated
3 Slave within the bus line
4 Slave at the bus line end, bus termination with 120 Ω resistors
The following photo shows a wiring example "master within the bus line", wired at the COM1
bus connector of the terminal base:
If the bus is operated with several masters, the pull-up and pull-down resistors
may only be activated at one master.
The earthing of the cable shields of the bus lines are described in the CS31 system bus
(PM57x, PM58x and PM59x)
Ä
Chapter 2.6.4.8 “CS31 System Bus” on page 1282.
2.6.4.7 Serial Interface COM2 of the Terminal Bases
The serial interface COM2 is not available at:
Processor modules with type designator -2ETH (e. g. PM591-2ETH)
Processor modules PM56xx
The serial interface COM2 is connected via a 9-pole D-sub connector. It is not intended to use
COM2 to establish a CS31 system bus. It is configurable for RS-232 or RS-485 and can be
used for
online access
a free protocol
Modbus RTU, master and slave
If the RS-485 bus is used, each interconnected bus line (each bus segment) must be electrically
terminated. The following is necessary:
2 resistors of 120 Ω each at both line ends (to avoid signal reflections)
a pull-up resistor at RxD/TxD-P and a pull-down resistor at RxD/TxD-N. These 2 resistors
care for a defined high level on the bus, while there is no data exchange.
System Assembly, Construction and Connection
AC500 (Standard) > Connection and Wiring
2019/04/173ADR010121, 13, en_US1280

Table of Contents

Related product manuals