Parameter Value
Fuse for UP3 10 A fast
Demagnetization with inductive DC load Via internal varistors (see figure below this
table)
Output switching frequency
With resistive load On request
With inductive loads Max. 0.5 Hz
With lamp loads 11 Hz max. at 5 W max.
Short-circuit-proof / overload-proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short circuit/
overload
Resistance to feedback against 24 V signals Yes (software-controlled supervision)
Max. cable length
Shielded 1000 m
Unshielded 600 m
The following drawing shows the circuitry of a digital input/output with the varistors for demag-
netization when inductive loads are switched off.
2
1
UPx (+24 V)
ZPx (0 V)
Fig. 136: Digital input/output (circuit diagram)
1 Digital output
2 Varistors for demagnetization when inductive loads are turned off
Technical Data of the Configurable Digital Inputs/Outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is
done by interrogating or allocating the corresponding channel.
Parameter Value
Number of channels per module 8 inputs/outputs (with transistors)
Distribution of the channels into groups 1 group for 8 channels
If the channels are used as inputs
Channels DC0...DC07 Terminals 2.0...2.7
If the channels are used as outputs
Channels DC0...DC07 Terminals 2.0...2.7