ABB AC500 PLC - Measuring Ranges; Voltage Input Ranges; Bipolar Voltage Input Range, Measuring Bridge

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED State Color LED = OFF LED = ON LED flashes
Inputs
I0...I3 and
I4...I7
Analog input Yellow Input is OFF Input is ON
(brightness
depends on
the value of
the analog
signal)
--
UP Process
voltage
24 VDC via
terminal
Green Process
voltage is
missing
Process
voltage OK
--
CH-ERR2 Channel
error, mes-
sages in
groups
(analog
inputs com-
bined into the
groups 2 and
4)
Red No error, or
process
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
group
CH-ERR4 Red
CH-ERR *) Module error Red -- Internal error --
*) Both LEDs CH-ERR2 and CH-ERR4 light up together
Measuring Ranges
Voltage Input Ranges
Bipolar Voltage Input Range, Measuring Bridge
Range -50 ... +50
mV
-500 ...
+500 mV
-1 ... +1 V -5 ... +5 V -10 ... +10
V
Common
Mode
Voltage
Overflow > 58.7945 > 587.9449 > 1.17589 > 5.8794 > 11.7589 > 20.0000
Measured
value too
high
58.7945
:
50.0018
587.9449
:
500.0181
1.17589
:
1.00004
5.8794
:
5.0002
11.7589
:
10.0004
Normal
range
Normal
range or
Measured
value too
low
50.0000
:
0.0018
500.0000
:
0.0181
1.00000
:
0.00004
5.0000
:
0.0002
10.0000
:
0.0004
20.0000
:
0.0008
0.0000 0.0000 0.0000 0.00000 0.0000 0.0000
-0.0018
:
-50.0000
-0.0181
:
-500.0000
-0.00004
:
-1.00000
-0.0002
:
-5.0000
-0.004
:
-10.0000
-0.0008
:
-20.0000
Measured
value too
low
-50.0018
:
-58.7945
-500.0181
:
-587.9449
-1.00004
:
-1.17589
-5.0002
:
-5.8794
-10.0004
:
-11.7589
Underflow < -58.7945 < -587.9449 < -1.17589 < -5.8794 < -11.7589 < -20.0000
The represented resolution corresponds to 16 bits.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 495