Name Value Internal
value
Internal
value,
type
Default Min. Max. Max.
Substitute
value at
outputs
Bit 7 =
Output 7
Bit 0 =
Output 0
0...255 0...0xff BYTE 0x00 0 255 0x0Y06
Reserve 0...255 0...0xff BYTE 0x00 0 255 0x0Y07
Reserve 0...255 0...0xff BYTE 0x00 0 255 0x0Y08
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len = 10
Ext_User_Prm_Data_Const(0) =
0x04, 0x51, 0x00, 0x06, 0x01, 0x01, 0x00,
0x00, 0x00, 0x00
Diagnosis
E1...E4 d1 d2 d3 d4 Identifier
000...063
AC500
display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
FBP diag-
nosis
block
Class Interface Device Module Channel Error
Identifier
Error message Remedy
1
)
2
)
3
)
4
)
Module error
3 14 1...10 31 31 19 Checksum error in the
I/O module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 3 Timeout in the I/O
module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 40 Different hard-/firmware
versions in the module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 43 Internal error in the
module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 36 Internal data exchange
failure
Replace
I/O module
11 / 12 ADR 1...10
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 367