EasyManua.ls Logo

ABB AC500 PLC - Connection of Resistance Thermometers in 3-wire Configuration to the Analog Inputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 176: Connection of resistance thermometers in 2-wire configuration to the analog inputs
The following measuring ranges can be configured
Ä
Chapter 1.7.4.1.7 “Parameterization”
on page 897 and
Ä
Chapter 1.7.4.1.9 “Measuring Ranges” on page 909:
Pt100 -50 °C...+70 °C 2-wire configuration, 1
channel used
Pt100 -50 °C...+400 °C 2-wire configuration, 1
channel used
Pt1000 -50 °C...+400 °C 2-wire configuration, 1
channel used
Ni1000 -50 °C...+150 °C 2-wire configuration, 1
channel used
The function of the LEDs is described under Diagnosis and displays / Displays
Ä
Chapter
1.7.4.1.8 “Diagnosis and State LEDs” on page 903.
The module CI521-MODTCP performs a linearization of the resistance characteristic.
To avoid error messages from unused analog input channels, configure them as "unused".
Connection of Resistance Thermometers in 3-wire Configuration to the Analog Inputs
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow
through them to build the necessary voltage drop for the evaluation. For this, the module CI521-
MODTCP provides a constant current source which is multiplexed over the max. 4 analog input
channels.
The following figure shows the connection of resistance thermometers in 3-wire configuration to
the analog inputs AI0 and AI1. Proceed with the analog inputs AI2 and AI3 in the same way.
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/173ADR010121, 13, en_US886

Table of Contents

Related product manuals