Parameter Value
Reference potential for the inputs Terminals 1.9, 2.9 and 3.9 (ZP)
Indication of the input signals 1 LED per channel
Input signal voltage 24 VDC
Signal 0 -30 V...+5 V
Undefined signal +5 V ... +13 V
Signal 1 +13 V...+30 V
Input current per channel
Input voltage +24 V Typ. 7 mA
Input voltage +5 V Typ. 1.4 mA
Input voltage +15 V Typ. 3.7 mA
Input voltage +30 V < 9 mA
Input resistance Ca. 3.5 kW
Technical Data of the Analog Outputs
Parameter Value
Number of channels per module 2
Distribution of channels into groups 1 group for 2 channels
Connection of the channels AO0+...AO1+ Terminals 1.5...1.6
Reference potential for AO0+ to AO1+ Terminal 1.7 (AO-) for voltage output terminal
1.9, 2.9 and 3.9 for current output
Output type
Unipolar Current
Bipolar Voltage
Electrical isolation Against internal supply and other modules
Configurability -10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually)
Output resistance (load), as current output 0 W...500 W
Output loadability, as voltage output ±10 mA max.
Indication of the output signals 1 LED per channel (brightness depends on the
value of the analog signal)
Resolution 12 bits (+ sign)
Conversion error of the analog values
caused by non-linearity, adjustment error at
factory and resolution within the normal
range
Typ. 0.5 %, max. 1 %
Relationship between input signal and hex
code
Table Output ranges voltage and current
Unused outputs Are configured as "unused" (default value) and
can be left open-circuited
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1045