3
)
With "Module" the following allocation applies
depending on the master:
Module error: I/O bus or PNIO: 31 = module
itself; COM1/COM2: 1..10 = expansion 1..10
Channel error: I/O bus or PNIO = module type
(2 = DO); COM1/COM2: 1..10 = expansion
1..10
4
)
In case of module errors, with channel "31 =
Module itself" is output.
1.6.1.1.7 State LEDs
LED State Color LED = OFF LED = ON LED flashes
PWR Process
voltage
24 VDC via
terminal and
process
voltage via
I/O bus
Green CPU module
voltage or
external
24 VDC
supply voltage
is missing
I/O bus voltage
and external
24 VDC supply
voltage are
present (LED is
on after startup
of the module
(approx. 1 s))
---
ERR Channel or
module error
Red No error or
process
voltage is
missing
Serious error in
the module
Axis related
error
P0...P3 Pulse output Yellow Output = OFF Output = ON LED follows
the state of the
outputs,
depending on
frequency
I0...I3 Digital Input Yellow Input = OFF Input = ON ---
O0...O1 Reserved Yellow --- --- ---
1.6.1.1.8 Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Digital inputs 4 inputs (2 per axis) 24 VDC, can be used as
source inputs or as sink inputs
Input channels 0 and 2 Input signal used for axis enable and limit
switch
Input channels 1 and 3 Stop, configurable
Input data length 32 bytes
Function Modules > S500-eCo