ABB AC500 PLC - 1.6.1.1.7 State LEDs; 1.6.1.1.8 Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
)
With "Module" the following allocation applies
depending on the master:
Module error: I/O bus or PNIO: 31 = module
itself; COM1/COM2: 1..10 = expansion 1..10
Channel error: I/O bus or PNIO = module type
(2 = DO); COM1/COM2: 1..10 = expansion
1..10
4
)
In case of module errors, with channel "31 =
Module itself" is output.
1.6.1.1.7 State LEDs
LED State Color LED = OFF LED = ON LED flashes
PWR Process
voltage
24 VDC via
terminal and
process
voltage via
I/O bus
Green CPU module
voltage or
external
24 VDC
supply voltage
is missing
I/O bus voltage
and external
24 VDC supply
voltage are
present (LED is
on after startup
of the module
(approx. 1 s))
---
ERR Channel or
module error
Red No error or
process
voltage is
missing
Serious error in
the module
Axis related
error
P0...P3 Pulse output Yellow Output = OFF Output = ON LED follows
the state of the
outputs,
depending on
frequency
I0...I3 Digital Input Yellow Input = OFF Input = ON ---
O0...O1 Reserved Yellow --- --- ---
1.6.1.1.8 Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Digital inputs 4 inputs (2 per axis) 24 VDC, can be used as
source inputs or as sink inputs
Input channels 0 and 2 Input signal used for axis enable and limit
switch
Input channels 1 and 3 Stop, configurable
Input data length 32 bytes
Device Specifications
Function Modules > S500-eCo
2019/04/173ADR010121, 13, en_US648