ABB AC500 PLC - Connection of Resistance Thermometers in 2-wire Configuration

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.0
I0-
1.1
I0B
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I0A
2.8
UP
2.9
ZP
UP
ZP
Fig. 50: Connection example
The following operating mode can be configured
Ä
Chapter 1.5.2.2.2.6 “Parameterization”
on page 489 :
Digital input 24 V 1 channel used
Effect of incorrect input ter-
minal connection
Wrong or no signal detected,
no damage up to 35 V
For a description of the function of the LEDs, please refer to Diagnosis and displays / displays
Ä
Chapter 1.5.2.2.2.7 “Diagnosis” on page 493.
Connection of Resistance Thermometers in 2-wire Configuration
When resistance thermometers (Pt100, Pt1000, Ni1000, Cu50) are used, a constant current
must flow through them to build the necessary voltage drop for the evaluation. For this, the
module AI531 provides a constant current source which is multiplexed over the 4 analog chan-
nels.
UP
ZP
1.0
I0-
1.1
I0B
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I0A
2.8
UP
2.9
ZP
Pt100
Pt1000
Ni1000
Cu50
Fig. 51: Connection example
The following measuring ranges can be configured
Ä
Chapter 1.5.2.2.2.6 “Parameterization”
on page 489:
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US482