Range -10 ... +10 V 0 ... 20 mA 4 ... 20 mA Digital value
Decimal Hex.
:
-0.0058
:
:
:
-10.0000
3.9942
:
:
0
-10
-16
-4864
-6912
:
-27648
FFF6
FFF0
ED00
E500
:
9400
Output value
too low
-10.0058
:
-11.7589
-27664
:
-32512
93F0
:
8100
Underflow <-11.7589 <0.0000 -32768 8000
The represented resolution corresponds to 12 bit respectively 11 bit plus sign.
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 19 for L+ (+24 VDC) and terminal 20
for M (0 V)
Rated value 24 VDC
Current consumption 0.1 A + output load
Inrush current (at power-up) 0.05 A²s
Max. ripple 5 %
Protection against reversed voltage Yes
Protection fuse for L+ Recommended
Current consumption from 24 VDC power
supply at the terminals UP/L+ and ZP/M of
the CPU/bus module
Ca. 5 mA
Galvanic isolation No
Surge-voltage (max.) 35 VDC for 0.5 s
Max. power dissipation within the module 3.1 W
Weight Ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 435