12 Terminal unit
13 DIN rail
Sign for XC version
1.7.5.1.1 Intended Purpose
The PROFIBUS DP bus module is used as decentralized I/O module in PROFIBUS DP net-
works. Depending on the used terminal unit the network connection is performed either via 9-
pole female D-SUB connector or via 10 terminals (screw-type or spring terminals) which are
integrated in the terminal unit. The bus module contains 22 I/O channels.
The inputs/outputs are electrically isolated from the PROFIBUS DP network. There is no poten-
tial separation between the channels. The configuration of the analog inputs/outputs is per-
formed by software.
For usage in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
● 4 configurable analog inputs (2-wire/single-ended) or 2 configurable analog inputs (3-wire/
differential)
Resolution 12 bits plus sign
● 2 analog outputs
Resolution 12 bits plus sign
● 8 digital inputs 24 VDC in 1 group
● 8 digital outputs 24 VDC in 1 group, 0.5 A max.
● Fast counter
● Module-wise electrically isolated
● XC version for usage in extreme ambient conditions available
1.7.5.1.2 Functionality
Parameter Value
Interface PROFIBUS
Protocol PROFIBUS DP (DP-V0 and DP-V1)
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O
expansion modules attached
Through the expansion bus interface (I/O bus)
Rotary switches For setting the PROFIBUS ID for configuration
purposes (00h to FFh)
Fast counter Integrated, configurable operating modes
LED displays For system displays, signal states, errors and
power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply
voltage 24 VDC)
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
Required terminal unit
TU509, TU510, TU517 or TU518
Ä
Chapter
1.4.2 “TU509 and TU510 for Communication
Interface Modules” on page 149
Ä
Chapter
1.4.4 “TU517 and TU518 for Communication
Interface Modules” on page 158
Communication Interface Modules (S500) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 943