EasyManua.ls Logo

ABB AC500 PLC - Input Range Resistor

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input Range Resistor
Range Pt100 / Pt1000
-50...+70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Overflow > 80.0 °C > 450.0 °C > 160.0 °C
Measured value too
high
80.0 °C 450.0 °C
:
400.1 °C
160.0 °C
:
150.1 °C
Normal range 400.0 °C
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
0.0 °C 0.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
Measured value too
low
< -60.0 °C -50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
Underflow < -60.0 °C < -60.0 °C < -60.0 °C
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 4500
:
4001
1194
:
0FA1
1600
:
1501
0640
:
05DD
800
:
701
0320
:
02BD
Normal range 4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1038

Table of Contents

Related product manuals