Channel Parameters for the Analog Inputs (4x)
Name Value Internal value Internal
value, type
Default EDS Slot /
Index
Input 0,
Channel con-
figuration
see
Ä
Table 83 “C
hannel Con-
figuration”
on page 587
see
Ä
Table 83 “C
hannel Con-
figuration”
on page 587
BYTE 0 0x0Y09
Input 0,
Check
channel
see
Ä
Table 84 “C
hannel Moni-
toring”
on page 588
see
Ä
Table 84 “C
hannel Moni-
toring”
on page 588
BYTE 0 0x0Y0A
: : : : :
: : : : :
Input 3,
Channel con-
figuration
see
Ä
Table 83 “C
hannel Con-
figuration”
on page 587
see
Ä
Table 83 “C
hannel Con-
figuration”
on page 587
BYTE 0 0x0Y0F
Input 3,
Check
channel
see
Ä
Table 84 “C
hannel Moni-
toring”
on page 588
see
Ä
Table 84 “C
hannel Moni-
toring”
on page 588
BYTE 0 0x0Y10
Table 83: Channel Configuration
Internal value Operating modes of the analog inputs, individually configurable
0 (default) Not used
1 0 V...10 V
2 Digital input
3 0 mA...20 mA
4 4 mA...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50 °C...+400 °C
9 3-wire Pt100 -50 °C...+400 °C *)
10 0 V...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50 °C...+70 °C
15 3-wire Pt100 -50 °C...+70 °C *)
16 2-wire Pt1000 -50 °C...+400 °C
17 3-wire Pt1000 -50 °C...+400 °C *)
18 2-wire Ni1000 -50 °C...+150 °C
Device Specifications
I/O Modules > Digital/Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 587