Parameter Value
Degree of protection IP20
Dimensions 25.4 mm x 17.4 mm x 15.1 mm
Weight 5 g
Table 218: Terminal Block for Serial RS-485 Adaptor
Parameter Value
Type Screw clamp plug, wire connection from side
Usage for
Ä
Chapter 2.5.5.4 “TA562-RS - Serial RS-485
Adaptor” on page 1231
Ä
Chapter 2.5.5.5 “TA569-RS-ISO - Serial
RS-485 Isolated Adaptor” on page 1232
Ä
Chapter 2.5.5.6 “TA562-RS-RTC - Adaptor
with Serial RS-485 (COM2) and Real-time
Clock ” on page 1233
Conductor cross section
Solid 0.14 mm²...1.5 mm²
Flexible (with wire-end ferrule only) 0.14 mm²...1.5 mm²
Stripped conductor end 7 mm
Fastening torque 0.4 Nm
Degree of protection IP20
Dimensions 19.05 mm x 8.7 mm x 19.1 mm
Weight 5 g
Part No. Description Product Life Cycle Phase *)
1TNE 968 901 R3203 TA570, spare part set for
AC500-eCo processor mod-
ules, 3x6 pieces
Active
*) For planning and commissioning of new installations use modules in Active
status only.
2.6 AC500 (Standard)
2.6.1 System Data AC500
2.6.1.1 Environmental Conditions
Table 219: Process and supply voltages
Parameter Value
24 VDC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
120 VAC
Ordering Data
System Assembly, Construction and Connection
AC500 (Standard) > System Data AC500
2019/04/173ADR010121, 13, en_US1248