1.7.6.5.7 Parameterization
Parameters of the Module
Name Value Internal value Internal value,
type
Default
Module ID
1
)
Internal 7015 WORD 7015
Parameter length Internal 33 BYTE 33
Error LED / Fail-
safe function
see table
2
)
On 0 BYTE 0
Off by E4 1
Off by E3 3
On + failsafe 16
Off by E4 + fail-
safe
17
Off by E3 + fail-
safe
19
Remarks:
1
) With a faulty module ID, the module reports a "parameter error" and does not perform cyclic
process data transmission
Table 190: Error LED / Failsafe function
2
)
Setting Description
On Error LED lights up at errors of all error classes, Failsafe-
mode off
Off by E4 Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe-mode off
Off by E3 Error LED lights up at errors of error classes E1 and E2, Fail-
safe-mode off
On + Failsafe Error LED lights up at errors of all error classes, Failsafe-
mode on
Off by E4 + Failsafe Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe-mode on
Off by E3 + Failsafe Error LED lights up at errors of error classes E1 and E2, Fail-
safe-mode on
All values are validated during the parameterization of the CI506-PNIO according to the
appended expansion modules. In the case of error, a diagnostic message "parameter error" is
generated and the cyclic process data transfer is terminated.
Parameters of the 2 Serial Channels
Name Value Internal value Internal
value, type
Default
Behavior for serial channel
communication during
PROFINET communica-
tion fault
Stop communica-
tion and reset FIFO
0 BYTE 0
Continue serial
communication
1
Number of frames/data
blocks in reception FIFO
1...40 1...40 BYTE 1
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1090