1.7.6.3.4 Internal Data Exchange
Parameter Value
Digital inputs (bytes) 5
Digital outputs (bytes) 5
Counter input data (words) 4
Counter output data (words) 8
1.7.6.3.5 Addressing
The module reads the position of the rotary switches only during power-up, i. e.
changes of the switch position during operation will have no effect until the next
module initialization.
1.7.6.3.6 I/O Configuration
The CI502-PNIO stores some PROFINET configuration parameters (I/O device identifier, I/O
device type and IP address configuration). No more configuration data is stored.
The digital I/O channels are configured via software.
Details about configuration are described in Parameterization
Ä
Chapter 1.7.6.3.7 “Parameteri-
zation” on page 1054.
1.7.6.3.7 Parameterization
Parameters of the Module
Name Value Internal value Internal value,
type
Default
Module ID
1
)
Internal 7005 WORD 7005
Parameter length Internal 8 BYTE 8
Error LED / Fail-
safe function
(Table Error
LED / Failsafe
function
Ä
Fur-
ther information
on page 1054)
On 0 BYTE 0
Off by E4 1
Off by E3 3
On + failsafe 16
Off by E4 + fail-
safe
17
Off by E3 + fail-
safe
19
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1054