Parameter Value
Protocol CANopen Master, CAN2A, CAN2B
Transmission rate 10 kbit/s to 1 Mbit/s
Ambient temperature see:
System data AC500
Ä
Chapter 2.6.1 “System
Data AC500” on page 1248
System Data AC500 XC
Ä
Chapter 2.7.1
“System Data AC500-XC” on page 1309
Usable terminal bases
All TB5xx
Ä
Chapter 1.1.1 “TB51x-TB54x”
on page 4
Field bus connector Pluggable connector COMBICON, 5-pin
Technology Hilscher netX100
Indicators 5 LEDs
Internal power supply Via the communication module interface of the
terminal base
Current consumption from 24 VDC power
supply at the Terminal Base of the CPU
Typ. 65 mA
Number of Slaves Max. 126
Number of receive/transmit PDOs Max. 512 (respectively for receive and
transmit)
Total quantity of input and output data Max. 3584 byte (respectively for input and
output)
Weight Ca. 150 g
1.3.4.2.5 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 173 800 R0001 CM598-CN, communication module
CANopen master
Active
1SAP 373 800 R0001 CM598-CN, communication module
CANopen master, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
Communication Modules (AC500 Standard) > CANopen
2019/04/17 3ADR010121, 13, en_US 115