EasyManua.ls Logo

ABB AC500 PLC - Technical Data of the Digital Inputs; Technical Data of the Digital Outputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical Data of the Digital Inputs
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DI0 to DI7 Terminals 3.0 to 3.7
Reference potential for all inputs Terminals 2.9 ... 4.9 (Minus pole of the supply
voltage, signal name ZP)
Indication of the input signals 1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Input type (according EN 61131-2) Type 1
Input delay (0->1 or 1->0) Typ. 0.1 ms, configurable from 0.1...32 ms
Input signal voltage 24 VDC
0-Signal -3 V...+5 V
Undefined Signal > +5 V...< +15 V
1-Signal +15 V...+30 V
Ripple with signal 0 Within -3 V...+5 V
Ripple with signal 1 Within +15 V...+30 V
Input current per channel
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 2 mA
Input voltage +30 V < 8 mA
Max. cable length
Shielded 1000 m
Unshielded 600 m
Technical Data of the Digital Outputs
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DO0 to DO7 Terminals 4.0 to 4.7
Reference potential for all outputs Terminals 2.9 ... 4.9 (minus pole of the supply
voltage, signal name ZP)
Common power supply voltage For all outputs terminal 4.8 (plus pole of the
supply voltage, signal name UP3)
Output voltage for signal 1 UP3 (-0.8 V)
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/173ADR010121, 13, en_US976

Table of Contents

Related product manuals