EasyManua.ls Logo

ABB AC500 PLC - 1.3.8.1.6 Ordering Data; 1.3.8.2 CM589-PNIO(-4)

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Total quantity of input and output data CM579-PNIO < FW 2.4.8.0
1024 bytes input and output data per IO
device
but in total 3072 bytes input output data
CM579-PNIO = FW 2.4.8.0
1024 bytes input and output data per IO
device
but in total 4096 bytes input output data
CM579-PNIO > FW 2.4.8.0
1440 bytes input and output data per IO
device
but in total 4096 bytes input output data
Min. bus cycle 1 ms
Conformance class CC A
*) CM579-PNIO does not allow setting "Station name" by using PROFINET service "DCP SET
NameOfStation".
1.3.8.1.6 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 170 901 R0101 CM579-PNIO, PROFINET
communication module
Active
1SAP 370 901 R0101 CM579-PNIO-XC, PROFINET
communication module, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.3.8.2 CM589-PNIO(-4)
PROFINET I/O device
Integrated 2-port switch
XC version for use in extreme ambient conditions available
Device Specifications
Communication Modules (AC500 Standard) > PROFINET
2019/04/17 3ADR010121, 13, en_US 139

Table of Contents

Related product manuals