Parameter Value
Total quantity of input and output data CM579-PNIO < FW 2.4.8.0
1024 bytes input and output data per IO
device
but in total 3072 bytes input output data
CM579-PNIO = FW 2.4.8.0
1024 bytes input and output data per IO
device
but in total 4096 bytes input output data
CM579-PNIO > FW 2.4.8.0
1440 bytes input and output data per IO
device
but in total 4096 bytes input output data
Min. bus cycle 1 ms
Conformance class CC A
*) CM579-PNIO does not allow setting "Station name" by using PROFINET service "DCP SET
NameOfStation".
1.3.8.1.6 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 170 901 R0101 CM579-PNIO, PROFINET
communication module
Active
1SAP 370 901 R0101 CM579-PNIO-XC, PROFINET
communication module, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.3.8.2 CM589-PNIO(-4)
● PROFINET I/O device
● Integrated 2-port switch
● XC version for use in extreme ambient conditions available
Communication Modules (AC500 Standard) > PROFINET
2019/04/17 3ADR010121, 13, en_US 139