EasyManua.ls Logo

ABB AC500 PLC - 2.4.5.1 Calculation of the total Current Consumption

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Consumers over terminals L+ and M on the AC500 terminal base/AC500-eCo CPU:
CPU itself
I/O modules attached on the I/O bus
Communication modules attached (AC500 terminal base)
Consumers over the process supply voltage terminals ZP and UP of the AC500 Terminal
Units / the L+/M or UP/ZP terminals of the AC500-eCo I/O modules:
Digital I/O modules
Analog I/O modules
The two supply voltages can be provided by the same power supply unit. The CPU and the I/O
modules should, however, be fused separately. Of course also separate power supplies are
possible.
2.4.5.1 Calculation of the total Current Consumption
In the example, the AC500 control system consists of the following devices:
CPU PM5xx-ETH
4 communication modules
7 I/O modules (digital and analog)
As well as the required terminal bases and terminal units
Example
System Assembly, Construction and Connection
Overall Information (valid for complete AC500 Product Family) > Power Consumption of an Entire Station
2019/04/173ADR010121, 13, en_US1190

Table of Contents

Related product manuals