Table 175: Table Error LED / Failsafe function
Setting Description
On Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode off
Off by E4 Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode off
Off by E3 Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode off
On + Failsafe Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode on *)
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode on *)
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode on *)
*) The parameter Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.
Group Parameters for the Digital Part
Name Value Internal value Internal value,
type
Default
Input delay 0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE 0.1 ms
0x00
Detect short cir-
cuit at outputs
Off
On
0
1
BYTE On
0x01
Behaviour DO at
comm. error
1
)
Off
Last value
Last value 5 sec
Last value 10 sec
Substitute value
Substitute value
5 sec
Substitute value
10 sec
0
1
6
11
2
7
12
BYTE Off
0x00
Substitute value
at output
0...65535 0000h...FFFFh WORD 0
0x0000
Preventive
voltage feedback
monitoring for
DC0..DC7
2
)
Off
On
0
1
BYTE Off
0x00
Detect voltage
overflow at out-
puts
3
)
Off
On
0
1
BYTE Off
0x00
Remarks:
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1056