State LEDs
In case of overload or short-circuit, the outputs switch off automatically and try to switch on
again cyclically. Therefore, an acknowledgement of the outputs is not necessary.
LED State Color LED = OFF LED = ON
Inputs/ out-
puts C0...C7
Digital input or
digital output
Yellow Input/output = OFF Input/output = ON
UP Process
supply voltage
24 VDC via
terminal
Green Process supply
voltage is missing
Process supply
voltage OK and
initialization
terminated
CH-ERR1 Module Error Red No error Error
Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminals 1.8 for +24 V (UP) and 1.9 for 0 V
(ZP)
Rated value 24 VDC
Max. ripple 5 %
Absolute limits at XC version Above 60 °C: 20 VDC...30 VDC
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 VDC power supply at the Ter-
minal Base of the CPU
10 mA
Current consumption from UP at normal
operation / with outputs
10 mA + 5 mA per input
Inrush current from UP (at power up) 0.002 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Max. power dissipation within the module On request
Weight (without terminal block) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 339