Terminals
Type 1.8 2.8 3.8 4.8 1.9 2.9 3.9 4.9
TU515,
TU516
and
TU516-H
These terminals are internally connected
with assignment: process supply voltage
UP = +24 VDC
These terminals are internally connected
with assignment: process supply voltage
ZP = 0 V
TU542
and
TU542-H
These terminals
are internally con-
nected with assign-
ment: process
voltage UP = +24
VDC
Separate
process
supply
voltage
UP3 =
+24 VDC
Separate
process
supply
voltage
UP4 =
+24 VDC
These terminals
are internally con-
nected with assign-
ment: process
supply voltage ZP =
0 V
Separate
process
supply
voltage
ZP = 0 V
Separate
process
supply
voltage
ZP = 0 V
The assignment of the other terminals depends on the inserted decentralized communication
interface module (see the description of the respective module used).
1.4.3.1 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Number of channels per module Max. 32
Distribution of the channels into groups 4 groups of 8 channels each (1.0...1.7,
2.0...2.7, 3.0...3.7, 4.0...4.7), the allocation of
the channels is given by the inserted I/O
module
Rated voltage 24 VDC
Max. permitted total current 10 A, per separated process voltage terminal
or for internal connection of process voltages
Earthing Direct connection to the earthed DIN rail or via
the screws with wall mounting
Screw terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Spring terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Weight 200 g
Mounting position Horizontal or vertical
Terminal Units (AC500 Standard) > TU515, TU516, TU516-H and TU542 for I/O Modules