NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist
environments.
Protect unused connectors and slots with TA535 protective caps for XC devices
TA535
Ä
Chapter 1.8.4.6 “TA535 - Protective Caps for XC Devices”
on page 1172.
1.4.1.1 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Number of I/O channels per module Max. 24 (depending on the inserted bus
module)
Distribution of the channels into groups 3 groups of max. 8 channels each (1.0...1.7,
2.0...2.7, 3.0...3.7), the allocation of the chan-
nels is given by the inserted Ethernet bus
module
Network interface connector 2 RJ45, 8-pole
Rated voltage 24 VDC
Max. permitted total current 10 A via the supply terminals (UP, UP3 and
ZP)
Ethernet 10/100 base-TX or 100 base-TX (depending
on CI5xx module plugged in), 2x RJ45 socket
Earthing Direct connection to the earthed DIN rail or via
the screws with wall mounting
Screw terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Spring-type terminals Front terminal, conductor connection vertically
with respect to the printed circuit board
Weight 200 g
Mounting position Horizontal or vertical
Terminal Units (AC500 Standard) > TU507-ETH and TU508-ETH for Ethernet Communication Interface Modules
2019/04/173ADR010121, 13, en_US148