1.7.2.3.13 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Technical Data of the Module
Parameter Value
Rated supply voltage of the module 24 V DC (UP/ZP)
Current consumption of the module (UP) 15 mA
Process voltage UP
Rated value 24 VDC (for inputs and outputs)
Max. current loadability for the supply
terminals
10 A
Protection against reversed voltage Yes
Rated protection fuse at UP 10 A fast
Electrical isolation CS31 bus interface from the rest of the module
Inrush current from UP (at power-up) 0.040 A²s
Current consumption from UP at normal
operation / with outputs
0.1 A + max. 0.008 A per input + max. 0.5 A per
output
Connections Terminals 1.8 - 4.8 for +24 V (UP) and 1.9 - 4.9
for 0 V (ZP)
Max. power dissipation within the module 6 W (outputs unloaded)
Number of digital inputs 8
Number of configurable digital inputs/outputs 16
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Address setting With 2 rotary switches on the front panel
Diagnosis
Diagnosis and Displays
Ä
Chapter 1.7.2.3.11
“Diagnosis” on page 820
Operating and error displays 32 LEDs altogether
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40°C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.