Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range
Normal range or Measured value too low
27648
:
1
6C00
:
0001
0 0000
-1
:
-27648
FFFF
:
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow -32768 8000
Unipolar Voltage Input Range, Measuring Bridge, Digital Input
Range 0 ... +5 V 0 ... +10 V Digital input
Measured
value too high
5.8794
:
5.0002
11.7589
:
10.0004
Normal range 5.0000
:
0.0002
10.0000
:
0.0004
ON
0.0000 0.0000 OFF
Measured
value too low
-0.0002
:
-0.8794
-0.0004
:
-1.1759
Underflow < -0.8794 < -1.1759
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 32511
:
27649
7EFF
:
6C01