EasyManua.ls Logo

ABB AC500 PLC - 1.3.7.2.5 Ordering Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
State indication By 5 LEDs
PWR, RDY, RUN, STA, ERR
Usable CPUs
PM57x, PM58x, PM59x
Ä
Chapter 1.2.2.1
“PM57x (-y), PM58x (-y) and PM59x (-y)”
on page 65
Usable terminal bases
All TB5xx
Ä
Chapter 1.1.1 “TB51x-TB54x”
on page 4
Current consumption from 24 VDC power
supply at the terminal base of the CPU
Typ. 65 mA
Internal power supply Through the communication module interface
of the terminal base
Maximum number of supported slaves 125 (DPV0/DPV1)
Maximum number of total cyclic input data 5712 bytes
(Status information is separately managed)
Maximum number of total cyclic output data 5760 bytes
Maximum number of cyclic intput data 244 bytes/slave
Maximum number of cyclic output data 244 bytes/slave
Configuration data max. 244 bytes per slave
Parametrization data per slave 7 bytes/slave standard parameters
237 bytes/slave application specific parame-
ters
Maximum number of acyclic read/write 240 bytes per slave and telegram
Processor Hilscher netX100
Internal RAM memory 8 MB
External Flash memory 8 MB
Weight Ca. 150 g
Parameter Value
Interface socket 9-pin, D-sub socket
Transmission standard EIA RS-485 acc. to IEC 61158/61784, poten-
tial-free
Transmission protocol PROFIBUS DP
Transmission rate 9.6 kbit/s up to 12 Mbit/s
1.3.7.2.5 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 173 200 R0001 CM592-DP, communication module
PROFIBUS DP master, 12 MBit/s
Active
1SAP 373 200 R0001 CM592-DP, communication module
PROFIBUS DP master, 12 MBit/s,
XC version
Active
Technical Data
of the Interface
Device Specifications
Communication Modules (AC500 Standard) > PROFIBUS
2019/04/173ADR010121, 13, en_US132

Table of Contents

Related product manuals