ABB AC500 PLC - 1.6.2.1.7 Diagnosis

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 95: GSD file
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
25
0x07, 0x0E, 0x17, \
0x01, 0x02, \
0x00, 0x00, 0x00, 0x02, 0x10, 0x00, 0x0A,
0x00, \
0x00, 0x00, 0x00, 0x02, 0x10, 0x00, 0x0A,
0x00, \
0x00, 0x00, 0x00, 0x00;
1.6.2.1.7 Diagnosis
E1...E4 d1 d2 d3 d4 Identi-
fier
000...06
3
AC500 dis-
play
<− Display in
Class Comp Dev Mod Ch Err PS501 PLC
browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
FBP diag-
nosis block
Class Inter-
face
Device Module Channel Error
identi-
fier
Error message Remedy
1
)
2
)
3
)
4
)
3 14 1...10 31 31 19 Checksum error
in the I/O module
Replace I/O
module
11 / 12 ADR 1...10
3 14 1...10 31 31 9 Overflow diag-
nosis buffer
New start
11 / 12 ADR 1...10
3 14 1...10 31 31 26 Parameter error Check
master
11 / 12 ADR 1...10
3 14 1...10 31 31 11 Process voltage
too low
Check
process
voltage
11 / 12 ADR 1...10
Device Specifications
Function Modules > S500
2019/04/173ADR010121, 13, en_US666