1.6.2.1.7 Diagnosis
E1...E4 d1 d2 d3 d4 Identi-
fier
000...06
3
AC500 dis-
play
<− Display in
Class Comp Dev Mod Ch Err PS501 PLC
browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
FBP diag-
nosis block
Class Inter-
face
Device Module Channel Error
identi-
fier
Error message Remedy
1
)
2
)
3
)
4
)
3 14 1...10 31 31 19 Checksum error
in the I/O module
Replace I/O
module
11 / 12 ADR 1...10
3 14 1...10 31 31 9 Overflow diag-
nosis buffer
New start
11 / 12 ADR 1...10
3 14 1...10 31 31 26 Parameter error Check
master
11 / 12 ADR 1...10
3 14 1...10 31 31 11 Process voltage
too low
Check
process
voltage
11 / 12 ADR 1...10