Technical Data of the Module
Parameter Value
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Electrical isolation PROFIBUS interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Configurable digital inputs/outputs 8
Number of digital inputs 8
Number of digital outputs 8
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Setting of the PROFIBUS DP identifier With 2 rotary switches at the front side of the
module
Diagnose
See Diagnosis
Ä
Chapter 1.7.5.1.8 “Diagnosis”
on page 965
Operation and error displays 32 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 975