Fuse for S of the
melting
integrals in
A²s
I
Logic A
I
UPx A
Recommended fuse
Type Value
F1 CPU logic 1.000 » 0.4 - Quick 10 A
F2 Module Dig-
ital1
0.005 - 8.050 Quick 10 A
F3 Module Dig-
ital2
0.008 - 8.050 Quick 10 A
F4 Module Dig-
ital3
0.007 - 8.050 Quick 10 A
F5 Modules
Analog1 +
Analog2 +
Analog3 +
Analog4
0.130 - 0.820 Quick 10 A
2.4.6 Recycling and Disposal
Devices of AC500 product family must not be disposed as unsorted domestic waste. The
devices contain valuable raw material which can be recycled. Remove the battery - if existing.
Dispose the products according to the local regulations.
Devices of AC500 product family are free from pollutants and are no danger for the environ-
ment.
2.5 AC500-eCo
2.5.1 System Data AC500-eCo
2.5.1.1 Environmental Conditions
Table 207: Process and Supply Voltages
Parameter Value
24 VDC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
100 VAC
Voltage 100 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
230 VAC
Voltage 230 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
100...240 VAC wide range supply
Voltage 100 V...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
System Assembly, Construction and Connection
AC500-eCo > System Data AC500-eCo
2019/04/173ADR010121, 13, en_US1192