The inputs/outputs are electrically isolated from the CANopen network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
For use in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
1.7.1.2.2 Functionality
Parameter Value
Interface CAN
Protocol CANopen
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O
modules attached
Through the expansion bus interface (I/O bus)
Rotary switches For setting the CANopen Node ID for configura-
tion purposes (00h to FFh)
LED displays For system displays, signal states, errors and
power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply
voltage 24 VDC)
Transmission rates 10 / 20 / 50 / 125 / 250 / 500 / 800 kbit/s 1
Mbit/s Auto baudrate detection is supported
Bus connection Depending on used terminal unit TU510: 9-pin
D-sub connector TU518: 10-pin terminal block
Processor Hilscher netX100
Expandability Max. 10 S500 I/O modules
State display Module state: PWR/RUN, CN-RUN, CN-ERR,
E-ERR, I/O bus
Adjusting elements 2 rotary switches for generation of the node
address
Ambient temperature
System data AC500
Ä
Chapter 2.6.1 “System
Data AC500” on page 1248
System data AC500 XC
Ä
Chapter 2.7.1
“System Data AC500-XC” on page 1309
Current consumption UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit) Ca. 125 g
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Galvanic isolation CANopen interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/173ADR010121, 13, en_US702