LED Color State Description
Blinking Device sends/receives frames
Off ---
1.3.8.2.5 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Protocol PROFINET I/O RT
Bus connection 2 x RJ45 (PNIO1 and PNIO2), with integrated
2-port switch
Switch Integrated
Technology Hilscher netX100
Transfer rate 100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEE802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Bus length (segment length max.) 100 m
Indicators 5 LEDs
Usable terminal bases
All TB5xx
Ä
Chapter 1.1.1 “TB51x-TB54x”
on page 4
Supported alarm types Process alarm, diagnostic alarm, return of
SubModule, plug alarm, pull alarm
Current consumption from 24 VDC power
supply at the terminal base of the CPU
Typ. 85 mA
Internal supply Via the communication module interface of the
terminal base
Setting of the I/O device identifier With 2 rotary switches at the front side of the
module
Weight Ca. 170 g
Supported protocols RTC - real-time cyclic protocol, class 1
RTA - real-time acyclic protocol
DCP - discovery and configuration protocol *)
CL-RPC - connectionless remote procedure
call
LLDP - link layer discovery protocol
SNMP - simply network management protocol
MRP - MRP Client
Communication Modules (AC500 Standard) > PROFINET
2019/04/17 3ADR010121, 13, en_US 143