Parameter Value
COM interfaces, electrically
not isolated
Not applicable Not applicable
FBP interface 500 V 1.2/50 µs
Ethernet 500 V 1.2/50 µs
ARCNET 500 V 1.2/50 µs
200 V... 240 V circuits against
other circuitry
1350 V AC 2 s
100 V circuits against other
circuitry
820 V AC 2 s
100 V...240 V circuits against
other circuitry
1350 V AC 2 s
24 V circuits (supply, 24 V
inputs/outputs, analogue
inputs/outputs), if they are
electrically isolated against
other circuitry
350 V AC 2 s
COM interfaces, electrically
isolated
350 V AC 2 s
COM interfaces, electrically
not isolated
Not applicable Not applicable
FBP interface 350 V AC 2 s
Ethernet 350 V AC 2 s
ARCNET 350 V AC 2 s
2.5.1.4 Power Supply Units
For the supply of the modules, power supply units according to PELV specifications must be
used.
2.5.1.5 Electromagnetic Compatibility
Electromagnetic Compatibility
Device suitable for:
Industrial applications Yes
Domestic applications No
Immunity against electrostatic discharge
(ESD):
According to IEC 61000-4-2, zone B, crite-
rion B
Electrostatic voltage in case of air dis-
charge
8 kV
Electrostatic voltage in case of contact dis-
charge
4 kV, in a closed switch-gear cabinet 6 kV
1
)
System Assembly, Construction and Connection
AC500-eCo > System Data AC500-eCo
2019/04/173ADR010121, 13, en_US1194