Fig. 211: Wiring of a straight-through cable
CAUTION!
Risk of communication faults!
When using inappropriate cables, malfunctions in communication may occur.
Only use network cables of the categories 5 (Cat 5, Cat 5e, Cat 6 or Cat 7) or
higher within PROFINET networks.
2.5.4.6 Modbus RTU Connection Details
The Modbus RTU protocol is implemented in the AC500 Processor Modules.
Modbus is a master-slave (client-server) protocol. The client sends a request to the server(s)
and receives the response(s).
Available serial interfaces can work as Modbus interfaces simultaneously.
The Modbus client operating mode of an interface is set with the Function Block
COM_MOD_MAST.
The Modbus operating mode and the interface parameters are set in the PLC configuration.
Description of the Modbus protocol:
Supported standard PM55x and PM56x: EIA RS-485
PM57x, PM58x and PM59x: EIA RS-232 /
RS-485
Number of connection points 1 client
Max. 1 server with RS-232 interface
Max. 31 servers with RS-485
Protocol Modbus
Operating mode Client/server
Address Server only
Data transmission control CRC16
Data transmission speed Up to 187.500 baud
Encoding 1 start bit
8 data bits
1 parity bit, (optional) even, odd, mark or
space
1 or 2 stop bits
Max. cable length for RS-485 1.200 m at 19.200 baud
Technical data
System Assembly, Construction and Connection
AC500-eCo > Connection and Wiring
2019/04/173ADR010121, 13, en_US1220