EasyManua.ls Logo

ABB AC500 PLC - Channel Parameters for the Analog Outputs (2 x)

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 142: Channel Configuration
Internal value Operating modes of the analog inputs, individually configurable
0 (default) Not used
1 0...10 V
2 Digital input
3 0...20 mA
4 4...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50...+400 °C
9 3-wire Pt100 -50...+400 °C *)
10 0...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50...+70 °C
15 3-wire Pt100 -50...+70 °C *)
16 2-wire Pt1000 -50...+400 °C
17 3-wire Pt1000 -50...+400 °C *)
18 2-wire Ni1000 -50...+150 °C
19 3-wire Ni1000 -50...+150 °C *)
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent
analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are
configured in the desired operating mode. The lower address must be the even address
(channel 0). The next higher address must be the odd address (channel 1). The converted
analog value is available at the higher address (channel 1).
Table 143: Channel Monitoring
Internal Value Check Channel
0 (default) Plausib(ility), cut wire, short circuit
3 Not used
Channel Parameters for the Analog Outputs (2x)
Name Value Internal value Internal value,
type
Default
Output 0,
Channel configu-
ration
Table Operating
modes of the
analog outputs
Ä
Table 144 “Ch
annel Configura-
tion”
on page 901
Table Operating
modes of the
analog outputs
Ä
Table 144 “Ch
annel Configura-
tion”
on page 901
BYTE 0
Output 0, Check
channel
Table Channel
monitoring
Ä
Table 145 “Ch
annel Monitoring”
on page 901
Table Channel
monitoring
Ä
Table 145 “Ch
annel Monitoring”
on page 901
BYTE 0
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/173ADR010121, 13, en_US900

Table of Contents

Related product manuals